DK-XXC large-screen LCD wall-mounted gas alarm controller (hereinafter referred to as the controller), using a wall-mounted structure, can receive up to 16 (4 ~ 20) mA signal input, using high-precision CPU chip. It can be used to continuously monitor the gases in the environment, display the measured gas concentration according to the received input signals, set two levels of alarm values, and send out different sound and light signals according to different alarm levels when the measured gas concentration exceeds the standard. Through the LCD display, you can observe the gas type, gas concentration value,gas concentration unit, and channel status (offline, normal, low alarm, high alarm,fault, burst meter, etc.) of each channel in real time.
| Technical Parameters | |
|---|---|
| Material | High-strength cold-rolled steel plate, plastic spraying on the surface |
| Hardware | Advanced microprocessor technology, stable work, high measurement accuracy |
| Input connection | Can be connected to a variety of gas detectors |
| Input Signal | Supports 1-16 way (4-20)mA standard signal input (2-wire/3-wire gas transmitter) |
| Input Protection | Transmitter power supply overload protection |
| Self-test | Full function self-test |
| Built-in parameters | Built-in 30 common gases, alarm parameter query |
| Parameter setting method | Parameters can be set arbitrarily by computer and keypad |
| Fault Alert | Fault alarm for accessing transmitter |
| Measuring unit | Measuring and displaying various gas concentrations ppm;%LEL;%VOL etc |
| Power supply | AC (185-255V, 50Hz) |
| Output power supply | DC24V300mA/per channel |
| Working mode | Multi-channel centralised display |
| Backup power supply | 24V/14Ah (optional) |
| Wattage | 130W full load (8W per channel) |
| Function Operation | Setting, Hold, Query, Self-test, Reset, Mute |
| Sampling rate | 0.125s per channel |
| Channel Query | Overall setting/channel setting can be queried |
| Channel Setting | Channel switch, any gas type, range value, low alarm value, high alarm value, channel relay output can be set freely. |
| Channel lock | Lock a channel |
| Output signal | Synchronised 4-20mA per channel |
| Alarm record content | Time, channel, concentration, status |
| Alarm setting | Two levels of alarm, interval alarm (oxygen), over-limit alarm (other gases) |
| Alarm optical signal output | Equipped with total LED indication (normal, low alarm, high alarm, fault) |
| Alarm sound signal output | Sound alarms with different frequencies (low alarm, high alarm, fault, burst meter, error) |
| Alarm channel Switching outputs | One relay per channel with normally open and normally closed |
| Alarm common Switching outputs | 3 common relays (low alarm, high alarm, fault), any combination by channel |
| Contact capacity | DC24V/5A (default) or AC220V/5A |
| Upper computer communication signal | RS485 Modbus |
| Display Mode | LCD screen |
| Resolution | Intelligent display 1, 0.1 or 0.01 (determined by range) |
| Measurement accuracy | 0.1% |
| Wireless output | Equipped with WX-200 wireless module, it can transmit signals to centralised control system and upper computer wirelessly |