首页 > Product and Solution > Gas Monitor Control Panel > DK Controller (Wall Mounted)
DK Controller (Wall Mounted)
Product Overview

DK Controller (Wall Mounted) is a gas alarm controller designed according to the national standard GB16808, the controller adopts advanced modular structure, colour touch screen man-machine interaction technology, dual power supply technology, can be simultaneously connected to the 2-way gas detector, each channel has a low limit and high limit of two levels of linkage output, built-in alarm records, support for data uploading and record query. The controller is stable, with high measurement accuracy, and adopts wall-mounted installation structure, which can be widely used in fire-fighting, metallurgy, petrochemical, environmental protection and other industries.

Basic parameter
DK Controller (Wall Mounted) - Basic parameter
Technical Parameters
Scope of application Measurement of various gas concentrations, etc
Power supply AC (185~255)V, 50Hz, maximum full load 150W
Output power supply DC24V, 300mA for each channel
Working mode Multi-channel acquisition, standard 4, 8, 16, 32 channels
Backup power supply 24V7AH optional
Power 100W full load (5W per channel)
Operation Keys Touch Setting, Query, Mute
Sampling rate 0.125s per channel
Channel setting/query On-site setting/query: Channel switch, gas type, alarm and other parameters
Input Signal 4~20mA or 485 Bus
Output Signal Synchronous 4~20mA/per channel
Alarm Records Curve, table of values, cumulative
Alarm Setting Two levels of alarm, zone alarm (oxygen), over limit alarm (other gases)
Alarm optical signal output Acoustic, optical and liquid crystal display of gas concentration
Alarm sound signal output Two-stage sound and light integrated alarm (low limit + high limit)
Alarm channel switch output (1 5A per channel with normally open/closed/common) 1 channel synchronous 4~20mA signal output per channel
Alarm common switch output 1 common relay output (normally open dry contact) 1 RS485 upload signal, standard modbus RTU 1 Ethernet/Fibre Optic/Lora/2G/3G/4G Outputs
Contact capacity DC24V/5A (default) or AC220V/5A
Communication Signal RS485 Modbus (standard), wireless (optional)